*
Class A
arc fault protection
(protection of
people)
5
*
Class B
arc fault protection
(protection of
people and
systems)
5
*
Class C
arc fault protection
(protection of
people and
systems)
5
No special
requirement for
arc fault protection
Redundant switchgear* assembly
recommended.
New and separate assessment of the
protection goals for the protection of
people and systems!
Additional equipment of an active arc
fault system recommended
*
Class C AND active arc
fault protection
integrated and tested
as per DIN VDE
0660-600-2-1
With user/manufacturer
agreement for testing
with open door or cover.
In addition:
Suitable PPE against
the thermal effects of
arc faults IEC 61482-2
APC 1 or APC 2
*
Class C AND active arc
fault protection
integrated and tested
as per DIN VDE
0660-600-2-1
Doors and covers
properly closed
DEHNshort
DEHNcare
DEHNshort
*
Class C AND active arc fault protection
integrated and tested as per DIN VDE 0660-600-2-1
Doors and covers properly closed.
The active arc fault protection should be certified to
VdS 2344
(fire protection technology systems) and
2349
(reliable electrical installation) in order to be
accepted by property insurers.
DEHNshort
Switchgear assembly as per DIN EN 61436-2
Proof of inspection as per DIN EN 61439-2 supplement 1 in arc faults*
No measures
necessary
Technical
measures
necessary
(standard
requirements)
Technical
measures
necessary
(strict
requirements)
Technical
measures
necessary
(strict
requirements)
for DEHNarX analysis
Assessment of hazards and risks
e.g. as per DGUV-I 203-077
Shutdown always possible
Shutdown not possible
Distance
On the switchgear installation
2–4 hours
7–10 days
2–4 weeks
1–2 months
Seconds/minutes, not tolerable
Protection of people
Protection of people
System protection
System protection
Maintenance
3
Switchgear installation open
Operation
2
Switchgear installation closed
Availability
4
Tolerable downtime
Fire protection
Fire risk reduction
5
Maintenance
3
Switchgear installation open
Shutdown always possible
Shutdown not possible
Operation
2
Switchgear installation closed
Distance
On the switchgear installation
Availability
4
Tolerable downtime
Seconds/minutes, not tolerable
2–4 hours
7–10 days
2–4 weeks
1–2 months
Fire protection
Fire risk reduction
5
No measures
necessary
No special
requirement for
arc fault protection
Operation
2
Switchgear installation closed
Distance
Switchgear assembly as per DIN EN 61436-2
Operation
2
Switchgear installation closed
No measures
necessary
Technical
measures
necessary
(standard
requirements)
Technical
measures
necessary
(strict
requirements)
for DEHNarX analysis
Assessment of hazards and risks
e.g. as per DGUV-I 203-077
Operation
2
Switchgear installation closed
On the switchgear installation
Switchgear assembly as per DIN EN 61436-2
Proof of inspection as per DIN EN 61439-2 supplement 1 in arc faults*
No measures
necessary
No special
requirement for
arc fault protection
*
Class A
arc fault protection
(protection of
people)
5
Switchgear assembly as per DIN EN 61436-2
Proof of inspection as per DIN EN 61439-2 supplement 1 in arc faults*
Technical
measures
necessary
(standard
requirements)
Switchgear assembly as per DIN EN 61436-2
Proof of inspection as per DIN EN 61439-2 supplement 1 in arc faults*
Technical
measures
necessary
(strict
requirements)
*
Class C AND active arc
fault protection
integrated and tested
as per DIN VDE
0660-600-2-1
Doors and covers
properly closed
DEHNshort
Maintenance
3
Switchgear installation open
Shutdown always possible
No measures
necessary
No special
requirement for
arc fault protection
Switchgear assembly as per DIN EN 61436-2
Maintenance
3
Switchgear installation open
Shutdown not possible
Technical
measures
necessary
(strictest
requirements)
*
Class C AND active arc
fault protection
integrated and tested
as per DIN VDE
0660-600-2-1
With user/manufacturer
agreement for testing
with open door or cover.
In addition:
Suitable PPE against
the thermal effects of
arc faults IEC 61482-2
APC 1 or APC 2
for DEHNarX analysis
Assessment of hazards and risks
e.g. as per DGUV-I 203-077
Switchgear assembly as per DIN EN 61436-2
DEHNshort
PSAgS
Proof of inspection as per DIN EN 61439-2 supplement 1 in arc faults*
No special
requirement for
arc fault protection
Switchgear assembly as per DIN EN 61436-2
1–2 months
Availability
4
Tolerable downtime
*
Class B
arc fault protection
(protection of
people and
systems)
5
2–4 weeks
Proof of inspection as per DIN EN 61439-2 supplement 1 in arc faults*
Switchgear assembly as per DIN EN 61436-2
Availability
4
Tolerable downtime
*
Class C
arc fault protection
(protection of
people and
systems)
5
7–10 days
Proof of inspection as per DIN EN 61439-2 supplement 1 in arc faults*
Switchgear assembly as per DIN EN 61436-2
Availability
4
Tolerable downtime
Proof of inspection as per DIN EN 61439-2 supplement 1 in arc faults*
Switchgear assembly as per DIN EN 61436-2
*
Class C AND active arc
fault protection
integrated and tested
as per DIN VDE
0660-600-2-1
Doors and covers
properly closed
DEHNshort
2–4 hours
Availability
4
Tolerable downtime
Redundant switchgear* assembly
recommended.
New and separate assessment of the
protection goals for the protection of
people and systems!
Additional equipment of an active arc
fault system recommended
Seconds/minutes, not tolerable
Switchgear assembly as per DIN EN 61436-2
Availability
4
Tolerable downtime
Fire protection
Fire risk reduction
5
*
Class C AND active arc fault protection
integrated and tested as per DIN VDE 0660-600-2-1
Doors and covers properly closed.
The active arc fault protection should be certified to
VdS 2344
(fire protection technology systems) and
2349
(reliable electrical installation) in order to be
accepted by property insurers.
Switchgear assembly as per DIN EN 61436-2
DEHNshort
Proof of inspection as per DIN EN 61439-2 supplement 1 in arc faults*